Installation
2.5Installation
WARNING
Possible Electric
Shock
Hazard!
Do not connect AC source until all
other connections are made and
installation is complete.
2.5.1 AC Power Input Block
Remove the 4 screws and the AC block cover as shown in Illustration 2-11 for 
access to the AC input block. Save these screws and cover for later re-installation.
Attach main AC feed to the appropriate points as labled in Illustration 2-12.
Illustration 2-11 AC block access
Illustration 2-12 AC block feed point definition
The AC mains feed-point requires 240 Volts single phase with neutral 
(which allows for 120 Volt supply). The following is the AC feed-point 
supply requirements : 
240 VAC single phase @ 30 Amps
120 VAC single phase @ 15 Amps (Neutral wire)
Provide the appropriate supply feed to match these requirements. 
Consult the National Electrical Code for your area for proper conductor 
size and color.